Welcome To Know Our Products, We Can Offer You High Quality Products!
WhatsApp / WeChat:
Email:
Welcome To Know Our Products, We Can Offer You High Quality Products!
WhatsApp / WeChat:
Email:
ZJQ 75 Submersible Slurry Pump Motor Winding Moisture Diagnosis: Application of Polarization Index (PI) and Dielectric Absorption Ratio (DAR)
Release time:
2026-04-28
Author:
Source:
Abstract
ZJQ 75 Submersible Slurry Pump Motor Winding Moisture Diagnosis: Application of Polarization Index (PI) and Dielectric Absorption Ratio (DAR)
Subtitle: More accurate than single insulation resistance measurement – field test methods, interpretation criteria, and moisture treatment procedures
Introduction
The ZJQ 75 submersible slurry pump (75mm discharge) is widely used in mine dewatering, foundation pit drainage, and dredging. The motor operates in water or humid environments, making winding moisture ingress the most common cause of motor burnout. While insulation resistance testing with a megger is standard, it has limitations: readings are heavily influenced by temperature, humidity, and surface contamination, often failing to accurately reflect the true internal condition of the winding.
Polarization Index (PI) and Dielectric Absorption Ratio (DAR) are more reliable diagnostic methods. By measuring insulation resistance changes over time, they can distinguish between surface moisture, internal moisture, and insulation aging, avoiding misjudgment. Hebei Xingou Machinery Equipment Co., Ltd. has extensive field experience applying these techniques. This article covers the principles, test methods, interpretation criteria, and moisture treatment procedures for ZJQ 75 motor windings.
1. Why Single Insulation Resistance Measurement Is Insufficient
Insulation resistance testing (500V or 1000V megger) is common but has limitations:
| Limitation | Description |
|---|---|
| Surface contamination effect | Dust and oil in terminal box, when damp, create surface leakage currents, causing falsely low readings |
| Temperature effect | Insulation resistance decreases as temperature rises; readings at different temperatures are not directly comparable |
| Cannot distinguish type of moisture | Cannot tell if moisture is on the surface or internal, nor differentiate from aging |
| Low sensitivity | Early mild moisture may still show acceptable resistance while a hidden risk exists |
PI and DAR eliminate surface leakage and temperature effects by measuring the rate of change of insulation resistance over time, providing much better diagnostic accuracy.
2. Principles of Polarization Index (PI) and Dielectric Absorption Ratio (DAR)
When DC voltage is applied to insulation, the current consists of three components:
Capacitive charging current: decays rapidly (within seconds)
Absorption current: caused by dielectric polarization, decays slowly (tens of seconds to minutes)
Leakage current: steady, reflects true insulation resistance
Insulation resistance readings combine absorption and leakage currents. The ratio of readings at different times reflects the polarization characteristics of the insulation and thus indicates moisture level.
Polarization Index (PI) = Insulation resistance at 10 minutes / Insulation resistance at 1 minute
Dielectric Absorption Ratio (DAR) = Insulation resistance at 60 seconds / Insulation resistance at 15 seconds
For dry, good insulation, absorption current decays slowly, so PI and DAR are high. When moisture is present, leakage current increases, the absorption current proportion decreases, and PI/DAR become low.
3. Field Test Procedure
3.1 Tools Required
| Tool | Specification |
|---|---|
| Megger (insulation tester) | 500V or 1000V, with timing function (15s, 60s, 600s readings) |
| Thermometer | Measure ambient and winding temperature |
| Discharge rod | For discharging after test |
| Record sheet | Log time, temperature, readings |
3.2 Test Steps
| Step | Action | Key points |
|---|---|---|
| ① Lockout | Disconnect power, verify zero voltage | Lock/tag |
| ② Discharge | Discharge motor terminals with discharge rod | Eliminate residual charge |
| ③ Clean surface | Wipe terminal box and insulators with dry cloth | Prevent surface leakage |
| ④ Connect | Connect megger L lead to winding, E lead to motor frame | Ensure good contact |
| ⑤ Measure | Start test, record resistance at 15s, 60s, 600s | Maintain stable speed |
| ⑥ Calculate | DAR = R60 / R15; PI = R600 / R60 | — |
| ⑦ Discharge again | Discharge terminals | Safe restoration |
3.3 Precautions
Measure and record winding temperature before the test
Insulation resistance values need temperature correction to a common reference (e.g., 20°C), but PI and DAR are temperature‑insensitive
For large motors, charging time is longer; ensure sufficient test duration
4. Interpretation Criteria
4.1 Polarization Index (PI) Criteria (for medium/large motors)
| PI value | Insulation condition | Recommendation |
|---|---|---|
| ≥ 2.0 | Good | Normal operation |
| 1.5 – 2.0 | Suspect | Increase monitoring, schedule drying |
| 1.0 – 1.5 | Poor | Arrange drying |
| < 1.0 | Severely wet | Immediate drying, risk of breakdown |
4.2 Dielectric Absorption Ratio (DAR) Criteria (all motors)
| DAR value | Insulation condition | Recommendation |
|---|---|---|
| ≥ 1.3 | Good | Normal operation |
| 1.0 – 1.3 | Suspect | Monitor closely |
| < 1.0 | Moist or aged | Further analysis or drying needed |
Note: PI/DAR values that are too low generally indicate moisture or contamination. Abnormally high PI (e.g., >4) may indicate brittle aging of insulation, also requiring attention. If insulation resistance itself is very high (>1000 MΩ) but PI is low, suspect surface contamination or improper test method – clean and retest.
4.3 Combined Assessment
| Insulation resistance (MΩ) | PI / DAR | Diagnosis | Action |
|---|---|---|---|
| > 100 | ≥ 2.0 | Good | Normal |
| 10 – 100 | 1.0 – 1.5 | Slight moisture | Plan drying |
| 1 – 10 | < 1.0 | Significant moisture | Immediate drying |
| < 1 | — | Severe moisture or breakdown | Disassemble, dry, possibly rewind |
5. Moisture Treatment Procedure
When PI or DAR is below standard, follow these steps:
| Step | Action | Note |
|---|---|---|
| ① Clean/dry surface | Wipe terminal box, insulators with alcohol | Eliminate surface leakage |
| ② Retest | Measure PI/DAR again | If improved, surface moisture only |
| ③ Internal drying | If still below standard, dry windings | See methods below |
| ④ Retest after drying | Confirm PI ≥ 2.0 | — |
| ⑤ Restore | Measure insulation resistance one last time | Only start if合格 |
5.1 Field Drying Methods
| Method | Application | Key points |
|---|---|---|
| Natural ventilation | Mild moisture | Open terminal box, ventilate for 24-48 hours |
| Infrared lamp | Moderate moisture | Place lamps 30-50 cm from winding, keep temperature 70-80°C |
| Short‑circuit current drying | Severe moisture | Block rotor, apply low‑voltage high current to self‑heat (professional only) |
| Forced hot air | Severe moisture | Use industrial hot air blower into motor, temperature ≤80°C |
6. Case Study: ZJQ 75 Moisture Diagnosis at an Iron Mine
Background: A ZJQ 75 pump was idle for two weeks during the rainy season. Upon restart, it tripped. Field megger reading showed 8 MΩ (rated 380V, requirement ≥1 MΩ). By conventional standards, this seemed usable, but the user was concerned.
Further diagnosis: Hebei Xingou Machinery technicians performed a PI test.
Results:
R15 = 4 MΩ
R60 = 6.5 MΩ
R600 = 8.2 MΩ
DAR = 6.5 / 4 = 1.63 (pass)
PI = 8.2 / 6.5 = 1.26 (below 2.0, fail)
Conclusion: Although insulation resistance met the minimum, the PI value indicated internal moisture. Drying was recommended.
Action: After 8 hours of hot air drying, PI rose to 2.5 and insulation resistance to 150 MΩ. The pump operated without further tripping.
Lesson: Relying only on insulation resistance would have misjudged the motor as acceptable, risking burnout during operation. PI testing identified the hidden issue in advance.
7. Routine Monitoring Recommendations
| Measure | Frequency | Purpose |
|---|---|---|
| Measure insulation resistance | Quarterly | Establish baseline |
| Annual PI/DAR test | Annually | Assess aging trend |
| Dry after prolonged shutdown | If idle >1 week | Prevent condensation |
| Inspect cable seal | Monthly | Prevent water ingress through cable |
Conclusion
For diagnosing moisture in ZJQ 75 submersible slurry pump motor windings, single insulation resistance measurement has limitations. Polarization Index (PI) and Dielectric Absorption Ratio (DAR) provide more accurate assessment, distinguishing between surface moisture, internal moisture, and insulation aging, offering reliable guidance for field maintenance. Hebei Xingou Machinery Equipment Co., Ltd. recommends incorporating PI/DAR testing into routine maintenance and establishing insulation condition records to detect hidden issues before motor burnout.
For on‑site moisture diagnosis or drying services, please contact Hebei Xingou Machinery’s technical team.
Key words:
ZJQ 75 submersible slurry pump, motor winding moisture, polarization index, dielectric absorption ratio, PI test, DAR test, insulation diagnosis, megger, Hebei Xingou Machinery, moisture treatment
Recommend Reading
The New Option for your Old Warman Slurry Pump
2026-03-23
Performance Benefits of Ceramic Wet Parts in High-Abrasion Slurry Pumps
2026-01-23
How to Choose the Right Slurry Pump Parts for Industrial Applications
2025-12-25






